Wall heating with clay: planning and installation step by step
Wall heating with clay warms you like a tiled stove: through radiation, at a low flow temperature and without swirling dust. The clay stores the heat, buffers indoor humidity and can even be used for cooling in summer. Here I show you how to proceed with the WEM system, from planning and installation to the finished surface. The figures come from the manufacturer's data sheets and installation instructions.
Which system suits your wall
There are three ways. In drywall construction you screw on climate elements: 25 mm thick clay boards with the heating pipe already inside. This is the fastest way with little moisture in the building, ideal for timber houses, stud walls and interior insulation. In the wet technique you fix Climate register or free pipe in toothed rails on the wall and plasters it in with clay. This suits solid walls, uneven old building walls and small areas. For rooms without heating water there is the electric climate element EL with 230 V.
You can combine wall, ceiling and floor freely. In old buildings, underfloor heating alone is often not enough; then you add wall or ceiling. If cooling is the priority, you preferably cover the ceiling.
Planning: area, temperature and heating circuits
The basis is a heating load calculation according to DIN EN 12831. WEM recommends a maximum flow temperature of 45 °C, with a heat pump rather around 35 °C. According to the data sheet, a climate element delivers about 85 W/m² at 35/30 °C and about 170 W/m² at 45/40 °C flow and return, measured with WEM clay plaster and at most 8 mm of plaster on top. The Climate register in plaster reaches about 100 and 200 W/m² at the same temperatures.
Cover the zones where you spend time: seating area, dining table, desk. With ceiling heights under 2,7 m, ceiling heating should run with a flow temperature of at most 35 °C. Insulate external walls with a U-value above 0,5 W/m²K beforehand, otherwise you heat the outdoors. Per heating circuit you connect at most five climate elements or six Climate register in series; with a free pipe it is at most 90 m. Each heating circuit gets an outlet on the heating circuit manifold.
Material for drywall construction
You need Climate elements MV in 200, 160 or 80 cm length at 62,5 cm width, i.e. 1,25, 1,0 and 0,5 m² of heating surface. You fill the remaining areas with WEM clay boards 25 mm, which you fix with retaining washers. Added to this are Metal composite pipe 16 x 2 mm and press fittings for the connections, clay adhesive and glass fibre fabric for the reinforcement and a fine plaster as the top layer. For the ceiling you use the Climate elements MV-D and clay board D, both stabilised with a dispersion and with additional fixing points.
Substrate and substructure
The wall or substructure must carry the weight and be level so that the boards do not become distorted when screwed. An MV 200 climate element weighs about 44 kg. Even out uneven walls with levelling plaster or battens. With timber battens, the battens at the joints should be at least 80 mm wide. It is best to reinforce metal studs with a clamped-in batten. In new builds, mount the elements before the floor build-up goes in; then the connecting lines disappear into the floor.
Fitting and connecting climate elements
Mount the elements with two people. Place the elements on a batten at the desired height, at least 8 cm above the floor, and leave space at the side for the pipe ends. Screw through the factory-fitted retaining washers, for example with countersunk screws 5 x 50 mm. If you add screws, watch the pipe route; it shows on the surface.
Cut the pipe ends to length, calibrate and deburr them. Between two elements you insert a piece of composite pipe with two pressed-on elbows. Do not bend by hand tighter than a 80 mm radius, and with a bending spring not tighter than 64 mm. Run the connecting lines to the manifold from the flow of the first element and from the return of the last.
Closing remaining areas with clay boards
Cover the areas without a climate element with WEM clay boards of the same thickness. Each board gets at least four fixing points with retaining washers. You can cut with a jigsaw or by cutting through the mesh on both sides with a utility knife and snapping the board over an edge. For sockets, use a core drill. Take dust protection measures when sawing.
Flush, fill and pressure test
Before plastering, flush each heating circuit individually and fill the system with demineralised water according to VDI 2035. Then comes the pressure test: close the ball valves on the manifold, pressurise to 5 to 6 bar, and after two hours restore the pressure because the pipe expands. After 24 hours no water may escape anywhere and the pressure must not have fallen by more than 0,1 bar. Record the result in the pressure test log.
Joints, reinforcement and fine plaster
First apply the retaining washers with clay adhesive and close joints under 3 mm at the same time. You plaster wider joints and the connecting pipes with Clay universal plaster . Let everything dry through. Then fill the whole area with clay adhesive up to at most 4 mm and lay the fine glass fibre fabric into the still soft plaster, overlapping at least 10 cm at the joints.
After drying, the top layer follows: Clay adhesive finish light with at most 3 mm or a clay fine plaster light or extra light. Very important: after each plaster layer, heat it dry immediately and ventilate the moisture away, with an open window or a condensation dryer. Afterwards you can leave the wall as it is or finish it with FarbTon clay paint .
Wet technique with climate register
With wet installation, you screw the Climate register to the wall with their toothed rails, shorten them if necessary and connect them with press couplings. You lay free pipe in toothed rails fixed at most every 100 cm, with at least 15 cm pipe spacing, in a meander or spiral pattern. After flushing and pressure testing you apply the Clay universal plaster in one or more layers and screed it off over the pipe. The next layer gets fabric over the whole area, at transitions to unheated areas at least 25 cm wide. The finish is formed by Clay adhesive finish light or a fine plaster. Here too: heat-dry after each layer. Clay plaster is not suitable in the splash zone or under tiles.
Control and hydraulic balancing
Each room gets a room thermostat that switches the actuators on the manifold. NYM 3 x 0,75 mm² cable is enough for wiring, 4 x 0,75 mm² for heating and cooling. On the manifold you set the flow rates of the heating circuits; this is hydraulic balancing according to DIN 18380. If your heat generator supplies higher temperatures than the wall heating needs, the control station on the manifold lowers the flow temperature.
Drill later without hitting the pipe
Before you hang a picture, place the Thermal foil onto the wall with the heating running. The warm pipes show up in colour and you place the drill between them. You fix heavy loads to the substructure.
Regional context and use in practice
I deliver the WEM wall heating throughout Germany. In northern Germany, wall heating is often found in timber frame and brick houses that are insulated on the inside: there it preferably sits on the interior insulation and makes the old walls warm and dry.
You will find climate elements, clay boards, climate registers, pipe, manifold, control, the matching clay plasters and dry underfloor heating in the wall heating category.
Buy wall heatingOpen questions
How much area do I need to cover with wall heating?
This is determined by the heating load calculation according to DIN EN 12831. Cover the zones where you spend time, such as the seating area, dining table and desk. If one surface is not enough, combine wall, ceiling and floor freely; in old buildings you often supplement underfloor heating this way.
Does the wall heating work with a heat pump?
Yes. WEM recommends a flow temperature of at most 45 °C; with a heat pump about 35 °C makes sense. According to the data sheet, a climate element delivers about 35 W/m² at 30/85 °C.
How thick will the plaster be on the climate elements?
The performance figures apply with WEM clay plaster and at most 8 mm of plaster. Typical are up to 4 mm of clay adhesive with fabric and above that up to 3 mm of finish or fine plaster.
Can I also cool with the wall heating?
Yes, the water-based systems also cool in summer. If cooling is the priority, cover the ceiling preferably: according to the data sheet, the MV-D climate element achieves about 52 W/m² of cooling output there at 25 °C room temperature. For heating and cooling you wire the room thermostats with NYM 4 x 0,75 mm².
May I drill into the wall later?
Yes, with the thermal foil you can see where the pipes run while the heating is on, and drill between them.
Sources and standards
Further links
Products in the shop
More items in Clay building
- Monument protection and clay building: age line, permit and typical mistakes
- Buy hemp insulation: hemp insulation batts for interior insulation, rafters and timber framing
- Hempcrete: mixture, application and insulation values for wall, floor and roof
- Interior insulation costs per m², wood fibre with clay vs. calcium silicate vs. drywall
- Lime plaster: properties, use and application inside and outside
- When clay does not work: limits, mistakes and decision rules
- Clay in interior finishing: a healthy indoor climate with natural building materials
- Clay, lime or cement: which binder is right for old buildings and timber framing?
- Advantages of clay building, healthy indoor climate, sustainability and building physics explained clearly
- Clay building: building and renovating with clay
- Clay boards in interior finishing: drywall construction with clay according to DIN 18948
- Buy fine clay plaster and YOSIMA design plaster: application, choice of colour and prices
- Clay paint on plasterboard: pre-treatment, consumption and painting
- Clay paint in interior finishing: mineral wall paint for a healthy indoor climate
- Clay mortar in clay building: masonry mortar and plastering mortar
- Clay plaster on concrete: preparation, primer and plaster thickness
- Clay plaster on gypsum plaster and old plaster: check, prime, plaster thinly
- Clay plaster on sand-lime brick and brick: plastering masonry correctly
- Clay plaster on Rigips and plasterboard: preparing the substrate correctly
- Applying clay plaster: the complete step-by-step guide
- Clay plaster costs per m², prices, material requirements and packs compared
- Renovating clay plaster: recognising types of damage, understanding causes and repairing correctly for the long term
- Clay plaster on different substrates: concrete, brick, wood and drywall
- Building up clay plaster: base coat, finishing coat and fine plaster
To take away: the free clay building diary with drying log.
Download free of charge